Producto
inicio > Producto
Disyuntores de corriente residual — CD series RCCB
Volver
Detalle


Applicable scope:

CD series residual current circuit breakers are applied to the lines with AC 50/60Hz,rated voltage of 230V(1P+N) or 400V(3P+N),and rated current of 100A.In case of electric shock or electric leakage current exceeds the specified value,the residual current circuit breaker can switch off the fault circuit in a very short time,protecting the safety of person and electric equipment.
Can be used in the industrial,commercial,high-rise buildings,civil residences and other places.

Number of poles

1P+N,3P+N
Rated current(In)
A
25,32,40,63,80,100
Rated operating voltage(Ue)
V
230V(1P+N),400V(3P+N)
Rated frequency
Hz
50/60
Rated insulation voltage(Ui)
V
500
Rated residual current (IΔn)
mA
10, 30, 100, 300
Rated residual switching on and breaking capacity(IΔm)
A
500(In=25A/32A/40A), 630(In=63A) ,800(In=80A),1000(In=100A)
Rated residual short-circuit current limit(IΔc)
A
6000  10000
Rated short-circuit current limit(Inc)
A
6000  10000
Rated switching on and breaking capaity(Im)
A
500(In=25A/32A/40A),630(In=63A) ,800(In=80A),1000(In=100A)
SCPD fuse
A
Matched silver wire
Maximun breaking time(IΔm)
S
0.3
Rated impulse withstand voltage(Uimp)
kV
6
Dielectric strength of main circuit
(1 min power frequency withstand voltage test)
kV
2.5
Pollution degree 

2
Electrical and mechanical life
times
4000
Residual current action indication

Standard operation condition Protection degree

IP20
Standard operation condition  Ambient temperature
-5℃~+40℃ and its average over aperiod of 24h does not exceed +35℃
Standard operation condition Storage temperature
-25℃to+55℃,for short periods not exceeding 24h,up to +70℃
Standard operation condition Altitude
m
≤2000
Terminal connection types

type cable,type U bus,type bus
Wiring terminal connection conductor
mm²
1.5~25
Wiring terminal copper size
mm²
25
Tightening torque
N*m
3.5
Installation mode

UsingTH3.5-7.5 profile installation, the title of installation face and vertical face is not greater than5°
Wiring incoming mode

upper and lower incoming is possible


Features

The residual current action uses pure electromagnetic type,its detection,discrimination and breaking action function is independent of the power supply voltage,overcoming the defects of poor anti-interference of electronic products,great fluctuation to the power grid voltage and protection failure due to broken neutral line,presenting reliable action.


Copyrigh Š 2018 Anhonor Electric Co., Ltd 浙ICP备18033980号-1